 PPS 10 Power System Data Sheet (Shelf System)
Features
* * * * * High reliability Simple installation and operation LCD display for self-guided controller operation Interfaces standards include RS232, and Form "C" dry alarm contacts with grouped alarms Intelligent battery management: * Temperature compensation (requires optional cables) * Programmable battery load testing with data logging * Symmetry (requires optional cables) * Programmable low voltage disconnect Optional Ethernet (SNMP compatible) interface module Natural convection cooled - no fans International standards compliance
* * *
Description
PPS 10 modular DC power shelf systems provide large power system features in cost-effective, rack-mounted form factors. These shelf power solutions provide rectification, system management, and power distribution while maintaining high reliability and offering flexibility for future expansion. The PPS 10 systems are based on hot-swappable rectifier modules with constant output power available at 1300 W per module. System management is accomplished through messages and alarms displayed on the system controller's (PCU/PCS) LCD screen and can also be displayed remotely via the PC-based PowComTM software package.
DEC 11, 2006
Page 1 of 4
www.power-one.com
PPS 10 Power System Data Sheet (Shelf System)
PPS 10-3900 System
An all-in-one 6U high shelf system that can be installed in both 19" and ETSI telecom cabinet solutions. The system subrack can accommodate up to 3 rectifier modules, a supervision module (PCU), and DC distribution with up to 2 battery breakers and 8 load breakers.
PPS 10-7800 System
An all-in-one 12U high shelf system that can be installed in 19" telecom cabinet solutions. The system subrack can accommodate up to 6 rectifier modules, a supervision module (PCS) and DC distribution with up to four battery breakers and 15 load breakers. Optional expansion subrack allowing max 12 modules (15.6 kW).
DEC 11, 2006
Page 2 of 4
www.power-one.com
PPS 10 Power System Data Sheet (Shelf System)
System Components
Rectifier Modules
The PPS 10 system utilizes plug-in rectifier modules that are based on a soft-switching approach. Features include 3 LEDs for rectifier status indication, thermal shutdown, and input overvoltage disconnection with an automatic reset.
Rectifier Features
Model PMP 13.48 SIC Voltage 48 VDC Power (max.) 1300 W Current (max.) 28 A
Supervision Modules
Advanced system supervision is accomplished using a microprocessor-based control module that allows both local and remote system monitoring.
PCU Features
* * * * * * * * Menu-guided operation RS232 interface for remote operation Battery management and testing Low voltage battery disconnect (LVBD) Partial load disconnect (PLD) Temperature compensation Battery symmetry measurement Optional Ethernet interface through SNMP and/or TCP/IP
PCS Features
All of the features listed under PCU above, plus: * Advanced battery management and testing * Digital signal collection via internal RS485 bus * Site programmable flash EPROM * Multiple language choices * Programmable alarms * Programmable logic functions and operations Monthly data logging
DEC 11, 2006
Page 3 of 4
www.power-one.com
PPS 10 Power System Data Sheet (Shelf System)
Input
Model Input
Inputs (max.)
PPS 10-3900 230/400V 3-phase 208-240V 1-phase Site configurable Single input 3 2 8 PCU 3 Yes
PPS 10-7800 230/400V 3-phase 208-240V 1-phase Site configurable Single input 6 4 15 PCS 4 Yes
Output
Rectifier Modules (max.) Battery Outs - MCB (100 A) Load Outs - MCB (2-63 A)
Features
Supervision
Battery
Battery Symmetry Inputs Low Voltage Battery Disconnection (LVBD)
Mechanical
Dimensions (WxHxD) Mounting Cable Entry
485 x 266 x 341 mm 19" or ETSI Top Yes N/A N/A Yes Yes
487 x 531 x 308 mm 19" Top Yes Yes Yes Yes Yes
Options
Temp. Comp. Charge Integrated Surge Arrestors Partial Load Disconnect Ethernet Network Interface Modem Interface
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
DEC 11, 2006
Page 4 of 4
www.power-one.com


▲Up To Search▲   

 